Enclosure Thermal Calculator
Enter your enclosure dimensions, material, installation conditions, and heat load to calculate the required heating and cooling capacity per IEC 60890.
Enclosure Dimensions & Material
External Dimensions
mm
mm
mm
W/m²K
Installation Conditions
All six faces are exposed to ambient air. Maximum passive heat dissipation.
Heat Load & Temperature Limits
W
Heating— winter / cold site
°C
°C
Cooling— summer / hot site
°C
°C
Results
Enclosure surface area is sufficient for passive heat dissipation.
Required heating capacity
0W
Heater output to maintain minimum internal temperature
Required cooling capacity
0W
Active cooling to maintain maximum internal temperature
How it’s calculated
Wall heat transfer
Q = k × ΔT × A × f
Cooling load
Q_cool = P_diss − Q_walls
Active cooling capacity
Q_air = (Q_cool / ΔT) × C_air
f = 1 (indoor) or 2 (outdoor). C_air = altitude-adjusted air constant. Based on IEC 60890.